Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The corrected water pressure calculations do not support the size of the water supplies to the individual apartments for systems 1 and 3. Reference Section 610.1, UPC 1994. Note also Section 608.1 and Appendix A, UPC 1994.
2. Provide a list of the plumbing fixtures for the laundry room. Reference Sections 202.0 ("private or private use") and 610.3, UPC 1994.
3. Provide a more legible copy of the calculations.