Permit Review Detail
Review Status: Completed
Review Details: PLUMBING
Permit Number - T05PL01092
Review Name: PLUMBING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/02/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The corrected water pressure calculations do not support the size of the water supplies to the individual apartments for systems 1 and 3. Reference Section 610.1, UPC 1994. Note also Section 608.1 and Appendix A, UPC 1994. 2. Provide a list of the plumbing fixtures for the laundry room. Reference Sections 202.0 ("private or private use") and 610.3, UPC 1994. 3. Provide a more legible copy of the calculations. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/12/2005 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 08/12/2005 | SUE REEVES | REJECT SHELF | Completed |