Permit Review Detail
Review Status: Completed
Review Details: PLUMBING
Permit Number - T05PL01092
Review Name: PLUMBING
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/14/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The corrected water pressure calculations do not support the size of the water supplies to the individual apartments for systems 1 and 3. Reference Section 610.1, UPC 1994. Note also Section 608.1, UPC 1994. 2. Clarify how the water is to be supplied to the studio apartments in buildings 3,4, 7, 8, 11, 12, 16, and 18. Reference Section 103.2.3, UPC 1994. 3. Show how water is to be supplied to the 1- and 2-bedroom apartments in system 1 (3 units) and system 2 (10 units). 4. The plumbing fixtures for the clubhouse and the laundry room are considered "public" and shall use the appropriate fixture units. Reference Sections 202.0 ("private or private use") and 610.3, UPC 1994. Restrict the maximum velocity for copper and PVC pipe to no more than 8 FPS. Reference Section A 6.1, UPC 1994; IAPMO IS 3-93, Section 610.0; and IAPMO IS 8-92, Section 610.1. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/14/2005 | GBONILL1 | OUT TO CUSTOMER | Completed |
07/14/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |