Plan Number: T05PI00015
Parcel: Unknown

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T05PI00015
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2005 RICHARD LEIGH DOT ENGINEERING REVIEW Denied RESUBMITTAL REQUIRED: Public sewer and paving plans.
The Engineering - Permits and Codes Section has reviewed the paving and does not recommend approval of the PIA Plan at this time. The following review comments need to be addressed in the next submittal.

1. Include on this plan set all of the offsite public improvements for Sierra Pantano.

2. Sheet 1: Provide recordation information (Book and Page) on cover sheet.

3. Sheet 1: Provide administrative address on cover sheet.

4. Sheet 2: (Detail A/2) Provide all details for the proposed catch basin at Camino Ensanada del Pantanowas. Provide a plan view and a cross section (parallel to roadway) of the catch basin. Additionally, bearing bars of grate must be placed parallel to the roadway.

5. Sheet 6: (Detail A/6) Indicate proposed material for keynote 1 and 2.

6. Sheet 6: Correct keynote for the proposed survey monument at Sta. 10+00 (Camino Sierra Pantano).

7. Sheet 8: Indicate pavement thickness of the proposed pavement widening on cross sections details C/8 and D/8. Do not refer to geotechnical report.

8. Sheet 8: (Detail E/8) Modify thickened edge as indicated on redlines.

9. Sheet 8: Why is detail F/8 shown on this plan set.

10. Sheet 8: (Detail G/8) Indicate the ramp width and maximum running slopes or provide a cross section indicating widths and slopes.

11. Sheet 8: Change title block to Permit and Codes title block (Sheet 2).

If you have any questions, or if you wish to meet, I can be reached at 791-3115 ext.448 or Richard.Leigh@tucsonaz.gov
11/28/2005 RICHARD LEIGH DOT ENGINEERING UTILITY AWARENESS NOTIFICATION Denied RESUBMITTAL REQUIRED: Public sewer and paving plans.
The Engineering - Permits and Codes Section has reviewed the paving and does not recommend approval of the PIA Plan at this time. The following review comments need to be addressed in the next submittal.

1. Include on this plan set all of the offsite public improvements for Sierra Pantano.

2. Sheet 1: Provide recordation information (Book and Page) on cover sheet.

3. Sheet 1: Provide administrative address on cover sheet.

4. Sheet 2: (Detail A/2) Provide all details for the proposed catch basin at Camino Ensanada del Pantanowas. Provide a plan view and a cross section (parallel to roadway) of the catch basin. Additionally, bearing bars of grate must be placed parallel to the roadway.

5. Sheet 6: (Detail A/6) Indicate proposed material for keynote 1 and 2.

6. Sheet 6: Correct keynote for the proposed survey monument at Sta. 10+00 (Camino Sierra Pantano).

7. Sheet 8: Indicate pavement thickness of the proposed pavement widening on cross sections details C/8 and D/8. Do not refer to geotechnical report.

8. Sheet 8: (Detail E/8) Modify thickened edge as indicated on redlines.

9. Sheet 8: Why is detail F/8 shown on this plan set.

10. Sheet 8: (Detail G/8) Indicate the ramp width and maximum running slopes or provide a cross section indicating widths and slopes.

11. Sheet 8: Change title block to Permit and Codes title block (Sheet 2).

If you have any questions, or if you wish to meet, I can be reached at 791-3115 ext.448 or Richard.Leigh@tucsonaz.gov
12/01/2005 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approv-Cond We have reviewed these plans and have the following comments:

1. Sheet 6 of 8 - Station 5+41.22 - This station has a keynote number 7 with it. The leader appears to point to an existing survey monument. Please address this prior to the final plans.

No further comments - Plan approved 12/1/05
12/05/2005 TAMI ACHONG ENGINEERING REVIEW Needs Review
12/05/2005 GARY WITTWER DOT LANDSCAPE REVIEW Denied You have not address my comments from the first reveiw. If you need to talk to me, please call me. No NPPO was submitted.
12/05/2005 DALE KELCH DOT TRAFFIC REVIEW Denied Traffic Engineering REJECTS this PIA submittal:

1. Unless this had been previously approved, all new sidewalks are to be 5' wide vice the 4' as called out in these plans. The corresponding shy space is reduced to 2'. See DS 3-01.0 fig 2 for guidance. Section F/8 still shows 4' sidewalk.

2. There are problems with the new sign and the existing sign to be relocated in the Escalante ROW adjacent to lot 1. The problems are delineated on the redlines. Said signs show on plan sheets 3, 6.



D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
12/19/2005 TAMI ACHONG PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
12/19/2005 TAMI ACHONG PIA COORDINATOR OUT TO CUSTOMER Approved