Plan Number: T05PI00013
Parcel: Unknown

Address:
7675 E 22ND ST

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T05PI00013
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2005 GARY WITTWER DOT LANDSCAPE REVIEW Approved Don't forget that if you are doing NPPO mitigation on site that a landscape and irrigation plan must be submitted if you are working within the ROW. Please note that you can not place private water lines under public streets.
11/07/2005 Blanca Espino DOT ENGINEERING REVIEW Denied 1. Please include a response letter with the next submittal that states how all comments have been addressed. Include plans/redlines from previous plan submittal.

2. Sheet 1, The Cover Sheet should reflect the approved Final Plat. Submit a copy of the last approved rezoning conditions and plat. Correct all sheets that are effected by this change.

3. Sheet 2, Indicate a dimensioned ramp detail cross section for details 1, 2 and 3. See redlines for corrections.

4. Sheet 9, Detail dimension and title do not match. Add note: No Parking required for 41.5 right of way as per Development Services Department. Correct and revise.
11/14/2005 TAMI ACHONG ENGINEERING REVIEW Needs Review
11/14/2005 THAD HARVISON DOT ENGINEERING UTILITY AWARENESS NOTIFICATION Needs Review 1. Please include a response letter with the next submittal that states how all comments have been addressed. Include plans/redlines from previous plan submittal.

2. Sheet 1, The Cover Sheet should reflect the approved Final Plat. Submit a copy of the last approved rezoning conditions and plat. Correct all sheets that are effected by this change.

3. Sheet 2, Indicate a dimensioned ramp detail cross section for details 1, 2 and 3. See redlines for corrections.

4. Sheet 9, Detail dimension and title do not match. Add note: No Parking required for 41.5 right of way as per Development Services Department. Correct and revise.
11/15/2005 TAMI ACHONG PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
11/15/2005 TAMI ACHONG PIA COORDINATOR OUT TO CUSTOMER Completed