Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T05PI00009
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/16/2005 DALE KELCH DOT TRAFFIC REVIEW Approved Traffic Engineering recommends APPROVAL of this PIA submittal:

1. The consultant should identify the W14-1 sign adjacent to lot 45 on sheet 11/13 as well as it is identified on sheet 4/13. This change can be made on the mylar submittal.

D. Dale Kelch, PE
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
12/16/2005 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved We have reviewed these plans and have no further comments. 12/16/05
12/20/2005 GARY WITTWER DOT LANDSCAPE REVIEW Approved
12/21/2005 RICHARD LEIGH DOT ENGINEERING REVIEW Denied SUBJECT: Empire Heights Improvements:
T05PI00009 (Second Review)

COMMENTS BY: Richard Leigh

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommend approval of the PIA Plan at this time. The following review comments need to be addressed in the next submittal.

1. Sheet 12, Detail G: Dimension footer for the header.

2. Sheet 12, Detail F, Mid-Block Vertical Curb: Indicate the placement of a vertical curb at the back of the curb access ramp.

3. Please darken the proposed improvements (sidewalk, curbing, drainage structures and etc.) on the plan views.
12/21/2005 RICHARD LEIGH DOT ENGINEERING UTILITY AWARENESS NOTIFICATION Approved SUBJECT: Empire Heights Improvements:
T05PI00009 (Second Review)

COMMENTS BY: Richard Leigh

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommend approval of the PIA Plan at this time. The following review comments need to be addressed in the next submittal.

1. Sheet 12, Detail G: Dimension footer for the header.

2. Sheet 12, Detail F, Mid-Block Vertical Curb: Indicate the placement of a vertical curb at the back of the curb access ramp.

3. Please darken the proposed improvements (sidewalk, curbing, drainage structures and etc.) on the plan views.
12/27/2005 TAMI ACHONG ENGINEERING REVIEW Needs Review
12/27/2005 TAMI ACHONG PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Approved
12/27/2005 TACHONG1 CONSTRUCTION ESTIMATE REVIEW Needs Review
12/27/2005 TAMI ACHONG PIA COORDINATOR OUT TO CUSTOMER Completed