10/17/2005 THAD HARVISON DOT ENGINEERING REVIEW Denied Must obtain utility clearances from all affected utilities.

1. Sheet 2 of 8: The plan indicates right-of-way abandoment for sidewalk? Shouldn't right-of-way be aquired from adjacent private property for sidewalk placement? Please address this issue accordingly.
2. Sheet 3 of 8: Provide recordation information (Book and Page) for right-of-way dedication.
3. Sheet 6 of 8: This sheet indicates typical scupper details b/b, a/a, for SCUPPER DETAIL, but it is not clear for which scupper? Please clarify.
4. Sheet 6 of 8: The previous red-lines indicated large grate and the revised sheet indicates a curb-opening? Has the drainage been revised?
5. Sheet 7 of 8: New Sheet, This sheet includes ramp details for 7" curbing, not 6" curbing. Please include the details that I sent in the last redlines that are for 6" curbing.
6. Sheet 7 of 8: Please call out "truncated domes" for all access ramps.
10/17/2005 THAD HARVISON DOT ENGINEERING UTILITY AWARENESS NOTIFICATION Denied Must obtain utility clearances from all affected utilities.

1. Sheet 2 of 8: The plan indicates right-of-way abandoment for sidewalk? Shouldn't right-of-way be aquired from adjacent private property for sidewalk placement? Please address this issue accordingly.
2. Sheet 3 of 8: Provide recordation information (Book and Page) for right-of-way dedication.
3. Sheet 6 of 8: This sheet indicates typical scupper details b/b, a/a, for SCUPPER DETAIL, but it is not clear for which scupper? Please clarify.
4. Sheet 6 of 8: The previous red-lines indicated large grate and the revised sheet indicates a curb-opening? Has the drainage been revised?
5. Sheet 7 of 8: New Sheet, This sheet includes ramp details for 7" curbing, not 6" curbing. Please include the details that I sent in the last redlines that are for 6" curbing.
6. Sheet 7 of 8: Please call out "truncated domes" for all access ramps.
10/21/2005 GARY WITTWER DOT LANDSCAPE REVIEW Denied You can not cross public streets with private water lines.
This note has not been taken care of.
10/31/2005 JBALDER1 PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
10/31/2005 DALE KELCH DOT TRAFFIC REVIEW Denied Traffic Engineering REJECTS this PIA submittal:

1. WG6 lines are to end at BCR not mid radius. (PMDM 3-8) 2nd request for this item. See attached redlines.

2. Enclose striped median island at the west end of Fortune Loop. Include YS24 diagonal striping in the gore @80' OC positioned such that here are at least 2 diagonal stripes. See PMDM sheets 4-2 and 4-4 for guidance. 2nd request for this item. See attached redlines.

3. Make leader for R1-1 sign at western leg of Fortune Loop to point at the sign.

D. Dale Kelch, PE