Plan Number: T05PI00005
Parcel: Unknown

Address: Unknown

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T05PI00005
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2007 SMONTIE1 UTILITY CLEARANCES COT STREETS DIVISION Denied Please submit utility clearance letters.
11/13/2007 SMONTIE1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied Please submit utility clearance letters.
11/13/2007 SMONTIE1 UTILITY CLEARANCES PC WASTEWATER MGMT Denied Please submit utility clearance letters.
11/13/2007 SMONTIE1 UTILITY CLEARANCES QUEST COMMUNICATION Denied Please submit utility clearance letters.
11/13/2007 SMONTIE1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied Please submit utility clearance letters.
11/13/2007 SMONTIE1 UTILITY CLEARANCES COX COMMUNICATION Denied Please submit utility clearance letters.
11/13/2007 SMONTIE1 UTILITY CLEARANCES SOUTHWEST GAS CORP Denied Please submit utility clearance letters.
11/13/2007 SMONTIE1 UTILITY CLEARANCES EL PASO NATURAL GAS Denied Please submit utility clearance letters.
11/13/2007 SMONTIE1 UTILITY CLEARANCES KINDER MORGAN ENERGY Denied Please submit utility clearance letters.
12/11/2007 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied We have reviewed this plan and have the following comments:

1. Please provide a Streets and Traffic Maintenace signature block.
2. Various streets call for sidewalk scuppers. What will be the erosion control at the outlets of theses scuppers?
3. Sheet p1 of p6 - You need to spell out "scupper" at station 23+56.35.

Landscaping

1. Sheet 8 of 9 - Detail 7 - Hose End Cap Detail - All ends need 1/2" plastic ball valve.
2. Sheet 8 of 9 - Detail 9 - Irrigation Trenching Detail - Traces wire needs to be #18 insulated tracers wire green wire attached 8" O.C.
3. Sheet 8 of 9 - Detail 12 - Pressure Reducing Valve - These need to be schedule 80 unions and the pressure reducing valve should be (Senninger Brand).
4. Sheet 9 of 9 - Detail 2 - Gate Valve - The union should be schedule 80 PVC ball valves instead of gates.
5. Sheet 9 of 9 - Detail 6 - Multi Port Emitter Box - This detail is not acceptable. Please see the city STD Drawing attached to the plan.

Electrical

Our Electric Shop did not recieve these plans for review. I have provided one of the sets given to me for them to review. The shop just got the plans on 12/11/07, so their comments will be late. You may wish to contact Ray Quihuis next week at 791-3154 to coordinate the electrical comments. Thank you.
12/12/2007 RICHARD LEIGH DOT ENGINEERING REVIEW Denied December 12, 2007


SUBJECT: La Estancia -Offsite, Wilmot Road, PIA Plan T05PI0005, I-2007-053

PROJECT REVIEWER: Richard Leigh

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan for the paving and drainage improvements only and does not recommend approval of the PIA Plan at this time. The following comments need to be addressed in the next submittal. Return redlined plans with next submittal.

1. Sheet 1: Include the plan number "I-2007-053" in the title blocks.

2. Sheet 1: Include DSD activity No. "T05PI00005" on cover sheet.

3. Sheet 1: Revise title block as indicated on redlines, see attached.

4. Include all line work used in legend.

5. Indicate the placement of survey monuments at roadway intersections.

6. Include the following paving notes:
q Drainage pipe shall conform to PC/COT SSPI Section 501or as directed by the engineer.
q Pipe bedding shall conform to PC/COT Standard Detail 108.

7. Sheet 8 & 9: Provide headwalls for the outlets of the proposed storm drains across Wilmot Road.

8. Sheet 8 & 9: Provide a detail of the headwalls using elliptical reinforced pipe.

9. Sheet 8 & 9: Call out the top of wall elevation for the headwalls of the proposed headwalls across Wilmot Road.

10. Sheet 10: Indicate the wing length of the proposed catch basin at Sta. 47+97.77, RT (Wilmot Road).

11. Sheet 20 & 21: Indicate the placement of header returns for the roadway intersections

12. Provide scour protection for the inlets of the proposed storm drains across Wilmot Road.

13. Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 791-3115 ext.448 or Richard.Leigh@tucsoz.gov
12/14/2007 GARY WITTWER DOT LANDSCAPE REVIEW Denied 1. I do not see any approval stamp from DSD for the Native Plant Preservation Ordinance. Has it been submitted?

2. Many of our rules have changed since 05. I am in discussion with Management on who will maintain this project long term. The City does not have the budget to accept any addition projects. We would need a written guarantee that the landscape and irrigation would be maintained by the developer. This would make the irrigation system private and create another problem with private irrigation lines in public roadways. (see your general note #13)

3. See Streets notes for irrigation comments.
12/21/2007 JOSE ORTIZ DOT TRAFFIC REVIEW Denied December 21, 2007
ACTIVITY NUMBER: T05PI00005
PROJECT NAME: La Estancis
PROJECT ADDRESS: Wilmot Rd/Los Reales
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal.

The following items must be revised or added to the plan.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. See redlines on the submitted drawings and address the additional redline comments. During the next submittal please re-submit the roll of redlines for back checking purposes.

3. Place the PIA and CDRC Case number on the cover sheet.

4. Add the following Signing General Notes 5(a) & 5(b) per PCDOT & TDOT Signing Manual (2002) (Chapter 1, Sheet 12) to the Plans.

5. Add the following Pavement Marking/Striping General Notes to the Plans:

'ALL STREET STRIPING & SIGNAGE TO BE COORDINATED WITH C.O.T. TRAFFIC ENGINEERING CALL 791-4259 A MINIMUM OF 48 HOURS PRIOR TO THE INSTALLATION OR REMOVAL OF ANY SIGNAGE OR STRIPING. ALL REQUIRED STRIPING AND SIGNAGE WILL BE INSTALLED AT THE CONTRACTOR'S EXPENSE. NEW STRIPING TO BE THERMOPLASTIC MATERIAL. USE 2" SQUARE-TUBE POST AND SQUARE TUBE POST FOUNDATIONS FOR SIGNING. BARRICADE PLAN MUST BE SUBMITTED TO THE CITY OF TUCSON TRAFFIC ENGINEERING FOR APPROVAL 48 HOURS IN ADVANCE OF ANY WORK IN PUBLIC RIGHT OF WAY.'

'ALL NON-SIGNALIZED INTERSECTION STREET NAMES MUST HAVE E-W BLOCK NUMBER ADDRESSES FOR E-W ROADWAYS AND N-S BLOCK NUMBER ADDRESSES FOR N-S ROADWAYS.'

'THE CITY SHALL NOT BE LIABLE FOR ANY ERRORS AND/OR OMISSIONS ON THESE PLANS. ITEMS NOT MEETING CITY STANDARDS SHALL BE REPAIRED/REPLACED BY THE DEVELOPER/CONTRACTOR AND AT NO COST TO THE CITY.'

'ALL WARNING SIGN PANELS SHALL BE FLUORESCENT YELLOW DIAMOND-GRADE (DG-CUBED OR EQUIVALENT) SHEETING. ALL SCHOOL ZONE SIGNS SHALL BE FLUORESCENT YELLOW-GREEN DIAMOND GRADE (DG-CUBED OR EQUIVALENT) SHEETING. ALL OTHER SIGN PANELS SHALL HAVE HIGH INTENSITY PRISMATIC TYPE IV SHEETING.'


If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov
12/26/2007 SMONTIE1 PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
12/26/2007 SMONTIE1 PIA COORDINATOR OUT TO CUSTOMER Completed