Plan Number: T05PI00004
Parcel: Unknown

Address:
7855 S WILMOT RD

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T05PI00004
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2005 THAD HARVISON DOT ENGINEERING REVIEW Denied Please see the attached comments:

1. Page 1 of 10: The Book and Page must be placed as indicated in the redlines.

2. Page 1 of 10: Provide project administrative address (Previous comment #13).

3. Page 1 of 10: Use correct title block (Previous comment #Previous comment # 2).

4. Page 3 of 10: Is the proposed pavement structural section no.1 based on a geotech report?

5. Page 4 of 10: Detail the proposed scupper (Previous comment # 8).

6. Page 4 of 10: Sidewalk must be at least 3-feet behind curbing.

7. Page 4 of 10: Use the curb access detail included on the redlines. In addition, truncated domes must be included on all ramps per Federal ADA requirements.

8. Page 6 of 10: Will a drainage channel be built as part of these plans?

9. Page 6 of 10: Per the approved Tentative Plat, the channel must be fully lined. Please revise.

10. Page 6 of 10: Per the approved Tentative Plat, the channel must have railing along the north side of the channel?. Please revise.

11. Page 6 of 10: Provide maintenance ramps into and out of the proposed channel.

12. Page 6 of 10: The proposed detention basin bleed pipe is not allowed in the r/w. Please remove.

13. Page 6 of 10: Provide barricade railing on both sides of the box culvert.

14. Page 6 of 10: Where will the small tributary flow (just south of the culvert and along the east side of Wilmot Rd.) be drained into?

15. Page 6 of 10: Provide Development Services Department Floodplain Use Permit number for the proposed channel and box culvert. This number must be noted on this sheet and on the cover sheet.

16. Page 6 of 10: Will solid concrete be used along the overbanks of the proposed channel?

17. Page 1 of 10: Please include the extent of the proposed channel on project description plan view.
06/30/2005 THAD HARVISON DOT ENGINEERING UTILITY AWARENESS NOTIFICATION Denied Please see the attached comments:

1. Page 1 of 10: The Book and Page must be placed as indicated in the redlines.

2. Page 1 of 10: Provide project administrative address (Previous comment #13).

3. Page 1 of 10: Use correct title block (Previous comment #Previous comment # 2).

4. Page 3 of 10: Is the proposed pavement structural section no.1 based on a geotech report?

5. Page 4 of 10: Detail the proposed scupper (Previous comment # 8).

6. Page 4 of 10: Sidewalk must be at least 3-feet behind curbing.

7. Page 4 of 10: Use the curb access detail included on the redlines. In addition, truncated domes must be included on all ramps per Federal ADA requirements.

8. Page 6 of 10: Will a drainage channel be built as part of these plans?

9. Page 6 of 10: Per the approved Tentative Plat, the channel must be fully lined. Please revise.

10. Page 6 of 10: Per the approved Tentative Plat, the channel must have railing along the north side of the channel?. Please revise.

11. Page 6 of 10: Provide maintenance ramps into and out of the proposed channel.

12. Page 6 of 10: The proposed detention basin bleed pipe is not allowed in the r/w. Please remove.

13. Page 6 of 10: Provide barricade railing on both sides of the box culvert.

14. Page 6 of 10: Where will the small tributary flow (just south of the culvert and along the east side of Wilmot Rd.) be drained into?

15. Page 6 of 10: Provide Development Services Department Floodplain Use Permit number for the proposed channel and box culvert. This number must be noted on this sheet and on the cover sheet.

16. Page 6 of 10: Will solid concrete be used along the overbanks of the proposed channel?

17. Page 1 of 10: Please include the extent of the proposed channel on project description plan view.
07/01/2005 GARY WITTWER DOT LANDSCAPE REVIEW Denied March 22, 2005

PIA – Landscape Review By Gary Wittwer
T05PI00004

Wilmot Road - MMLA

Comments:

Please address Native Plant Preservation Ordinance.
07/07/2005 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved
07/18/2005 TAMI ACHONG PIA COORDINATOR CUSTOMER CALLED Completed
07/18/2005 TAMI ACHONG PIA COORDINATOR OUT TO CUSTOMER Completed