Plan Number: T05PI00002
Parcel: Unknown

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T05PI00002
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2005 THAD HARVISON DOT ENGINEERING UTILITY AWARENESS NOTIFICATION Denied Documentation for Utility Awareness Notification not submitted
04/18/2005 THAD HARVISON DOT PERMITS & CODES REVIEW Denied Comments for Offsite - Menlo Park Mercado District:

1. Provide the following items on the cover sheet:

a. Maps and Plats Book and Page.

b. Project administrative address.

c. Add I-2005-022 to the Plan No. block.

2. Provide concrete sidewalks per Standard Detail 200 with no modifications.

3. Provide modified concrete driveway apron details.

4. Remove all comments that refer to other plans for information and/or construction details.

5. Identify all "No Parking" signs.

6. Show only sewer construction details for that portion in the private alley parking from Station 2+35.00 to 3+55.55.

7. Show the Docket and Page for the 20' X 20' Public Sewer Easement on Page 5 of 7.

8. Provide curb acess ramp details (second request).

9. Provide Utility Awareness Notification sheets (second request).
04/19/2005 THAD HARVISON DOT ENGINEERING REVIEW Denied Documentation for Utility Awareness Notification not submitted
04/27/2005 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied 1. Sheet 4 and Sheet 5 - Note 19 - Concrete Header should reference PC/COT SD213.
05/09/2005 DALE KELCH DOT TRAFFIC REVIEW Denied Traffic Engineering REJECTS this PIA:

1. Key note 25 (all sheets), striping is misspelled as "stripping."

2. Key note 25 states to see signing and striping plans. No such sheets are included in this plan set.

D. Dale Kelch, EIT
Senior Engineering Associate
Traffic Engineering Division
(520)791-4259x305
(520)791-5526 (fax)
dale.kelch@tucsonaz.gov
05/13/2005 GARY WITTWER DOT LANDSCAPE REVIEW Denied January 24, 2005

PIA – Landscape Review By Gary Wittwer
T05PI00002
Menlo Park Mercado District – Off-site

Comments:
If planting will take place in the ROW – please submit a Landscape and irrigation plan.
Please address NPPO. If already approved – please submit copy.
05/19/2005 TAMI ACHONG PIA COORDINATOR CUSTOMER CALLED Completed
05/20/2005 TAMI ACHONG PIA COORDINATOR OUT TO CUSTOMER Completed