Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05OT02991
Parcel: 131050030

Address:
5464 E 29TH ST

Review Status: Completed

Review Details: C OF O

Permit Number - T05OT02991
Review Name: C OF O
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2005 HEATHER THRALL ZONING REVIEW Approved
12/05/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
12/05/2005 JUDY SONKIN SIGNS REVIEW Approved