Permit Number: T05OT02927
Parcel: 11628001L

Review Status: Completed

Review Details: SITE

Permit Number - T05OT02927
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2005 JIM EGAN FIRE REVIEW Denied 1. Indicate connection of Starr Pass Drive and Tohono Ridge Drive on plan.
2. Indicate location of new/existing fire lane signs on plan.
3. Provide approved COT Water Plan for reloaction of fire hydrant Sht. LS103.
4. Minimum unobstructed width of Tohono Ridge Dr. Shall be 20 feet.Sht. LG 107.
12/07/2005 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens FOR: David Rivera
Senior Planner Principal Planner

PROJECT:T05OT02927
Marriot's Starr Pass
Landscape and Hardscape Improvements
Site Plan

Transmittal date: 1st Review 12-08-05

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. On sheet LS-103, provide an accessible pedestrian route to the bus stop canopy. Handicap ramps are missing at the sidewalk along the building and at the bus stop area.

2. All new handicap ramps must meet the following. Access ramps at crosswalks connecting to sidewalks must be provided. In addition Truncated Dome (early warning systems) must be added to all access ramps where transitioning from the pedestrian area to the vehicular use area or at HC access aisles transitioning to the sidewalk area.

3. On sheet LS-108 provide dimensioned plans indicating the existing right of way width, curb location, and sight visibility triangles for both sides of Starr Pass Blvd. The proposed walls appear to be located in the public right of way which is not allowed with out a temporary revocable easement provided by the City of Tucson.. You may contact Jim Rossi @ 791-4181 regarding revocable easements. Walls or signs cannot be located within a sight visibility triangle unless the structures are less than 30" in height. Provide elevation plans of the proposed walls clearly indicating the height of the proposed walls.


If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000.
12/12/2005 TERRY STEVENS ZONING HC SITE REVIEW Denied see zoning comments
12/13/2005 ANDREW CONNOR LANDSCAPE REVIEW Approved
12/13/2005 ANDREW CONNOR NPPO REVIEW Approved
12/14/2005 MATT FLICK ENGINEERING REVIEW Denied 1. Show dimensioning of public right-of-way.

2. Verify and show limits of public right-of-way.

3. All work in right-of-way requires a right-of-way permit or private improvement agreement (PIA) review and approval.

4. Temporary revocable easement (TRE) may be required for signage and planting in right-of-way.

5. Show and label roadway stationing on public roadways. Use established stationing from previous construction drawing (like I-2003-054).

6. Provide truncated domes on HC ramps.

7. Provide civil drawings for work in right-of-way.

8. Call out PC/COT Standard Detail numbers for all work in the public right-of-way.

9. Provide matchlines between all sheets that match to another sheet.

Matt Flick, PE
Engineering Manager

Final Status

Task End Date Reviewer's Name Type of Review Description
12/20/2005 SUE REEVES OUT TO CUSTOMER Completed
12/20/2005 SUE REEVES REJECT SHELF Completed