Parcel: 20914001C

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T05OT02789
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2005 ELIZABETH EBERBACH ENGINEERING REVIEW Denied DATE: November 23, 2005
SUBJECT: Floodplain Use Permit Engineering review for Ryan Airfield Hangars Parcel 22
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBERS: T05OT02789 / T05CM05529

SUMMARY: The Ryan field hangar plans were received on November 14, 2005, and the master Drainage Report was received by Engineering on November 15, 2005. Development Services Department Engineering Division has done a preliminary review of the received items and does not recommend approval of the Floodplain Use Permit application at this time until the following comments are addressed.

FLOODPLAIN USE PERMIT COMMENTS:
1) Provide addendum to the master drainage report that provides the following information for the A zone:
a) The depth of flow for the 100-year of event for the parcel.
b) Provide recommended minimum finished floor elevations for each building structure. If the depth varies at the different building locations on the parcel, assure that each building structure minimum FFE is 1 foot above the regulatory flow depth.
2) Label minimum FFE on the plan.
3) An elevation certificate will be required to be completed and submitted to the Development Services Department Engineering Division, after the pad elevations for each building is established as well as after the foundation is completed to show that the FFE meets the approved FFE recommended by the consultant. This will be further explained at next submittal.

If you have any further questions, you may contact me at 791-5550, extension 2204.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services Department

Final Status

Task End Date Reviewer's Name Type of Review Description
11/28/2005 DELMA ROBEY OUT TO CUSTOMER Completed