Permit Review Detail
Review Status: Completed
Review Details: FLOODPLAIN
Permit Number - T05OT02667
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/16/2005 | SUZANNE BOHNET | ENGINEERING | REVIEW | Denied | DATE: November 22, 2005 ACTIVITY NUMBER: T05OT02667 / T05CM05064 PROJECT NAME: El Capitan Townhome Repairs PROJECT ADDRESS: 342 N. Park Avenue PROJECT REVIEWER: Suzanne Bohnet FLOODPLAIN USE PERMIT IS DENIED RESUBMITTAL REQUIRED: SITE PLAN The following items must be corrected: 1. Add a note, indicating the structure lies within a mapped FEMA Special Flood Hazard Area Zone AE, referencing the FIRM panel number 04019C 2227K, effective date February 8, 1999. 2. Please include the Water Surface Elevation (WSE) on the Site Plan. From interpolation, the WSE for this structure is approximately 2400.2' above mean sea level (amsl) per the National Geodetic Vertical Datum (NGVD '29). 3. Add a note to the site plan indicating the vertical datum used for the finished floor elevation (FFE) and the WSE. 4. Please note the above requested information must be on the site plan. The site plan will not be approved unless the FFE and WSE for the structure have been provided. 5. Your resubmittal needs to include the site plan, the "blue" Floodplain Use Permit application card and the "white" building permit card (#T05CM05064). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/30/2005 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 11/30/2005 | SUE REEVES | REJECT SHELF | Completed |