Permit Number: T05OT02489
Parcel: 133300510

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T05OT02489
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2006 ANY ENGINEERING REVIEW Denied To: C.G. Urias DATE: March 2, 2006
Architect
6136 E. West Miramar Drive
Tucson, Arizona 85715

SUBJECT: Garigan Residence, 8821 E Appomattox St.
Site/Bldg. plan T05CM04729 (Second Review)
T14S, R15E, Section 05

RESUBMITTAL REQUIRED: Site/Bldg. Plan and Drainage Report.

The Development Plan (DP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site/Bldg. Plan:

1. Please include a response letter to the comments along with the corrected copies of the DP.
2. The FUP cannot be approved prior to the site/bldg. plan.
3. The FFE recommended in the DR does not match the FFE on the constructions plans. Use the elevation recommended in the DR and list the datum. Per pervious comment.
4. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
5. Show the appropriate openings in the block patio wall to allow the 100-year event to flow through per drainage report. Per pervious comment.
6. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16. Per pervious comment.
7. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17. Per pervious comment.
8. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.

Drainage Report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. List the datum used in the DR. The FFE recommended in the DR does not match the FFE on the constructions plans. It may be the same elevation using two different datums, however a conversion equation must be shown. Per previous comment.
3. Show the appropriate opening in the North patio wall to allow the 100-year event to flow through as discussed on our phone conversation.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@ci.tucsonaz.govs
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/8821 E Appomattox St Site-Bldg2

Final Status

Task End Date Reviewer's Name Type of Review Description
03/09/2006 DELMA ROBEY OUT TO CUSTOMER Completed
03/09/2006 SUE REEVES REJECT SHELF Completed