Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: FLOODPLAIN
Permit Number - T05OT02301
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/06/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | Provide a plot plan/site plan showing existing grades and proposed grades. The site is within a floodplain with a base flood elevation of 2524.69 feet NGVD 1929. The finished floor of the proposed structure must be at least one foot above the base flood elevation. Explain how this elevation will be achieved. A grading permit will be required if more than 1 foot of fill or if more than 50 cubic yards of fill must be placed on the site. Revise the building plan to indicate the finish floor elevation will be at or above the required elevation and provide a basis of elevation. If the basis of elevation uses a vertical datum other than NGVD 1929 provide the conversion calculations for the datum used. |
| 10/06/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | ADDITIONAL INFORMATION PROVIDED. ELEVATION CERTIFICATE REQUIRED. |