Permit Number: T05OT02192
Parcel: 113081750

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T05OT02192
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: October 6, 2005
ACTIVITY NUMBER: T05OT02192
PROJECT NAME: Duplex
PROJECT ADDRESS: 1125 East Blanton Drive
PROJECT REVIEWER: Patricia Gilbert

FLOODPLAIN USE PERMIT IS DENIED

RESUBMITTAL REQUIRED: SITE PLAN, DRAINAGE REPORT, FLOODPLAIN USE PERMIT APPLICATION

SUBMIT SITE PLAN WITH SITE PLAN APPLICATION

1. Add a note to the site plan referencing the FIRM panel number and the flood hazard zone. Indicate the parcel is entirely in a FEMA flood hazard area, Zone AE.

2. Indicate the finish floor elevation (FFE) and the water surface elevation (WSE) on the site plan.

3. Add a note to the site plan indicating the datum used for the FFE and the WSE found in the drainage report.

4. Please note a condition of this permit contains a requirement that the applicant, or the applicant's authorized representative, complete a FEMA Elevation Certificate and is returned to DSD Engineering prior to approval of special inspection.

DRAINAGE REPORT COMMENTS

1. Indicate the datum used for the FFE and the WSE. If two different datums are used show the conversions. The same datum must be used for the FFE and the WSE.

2. It is acknowledged that the FIRM map has been provided in the drainage report. For report clarity formally indicate the WSE for the project area, include the datum (see above comment).

Final Status

Task End Date Reviewer's Name Type of Review Description
10/07/2005 JMORALE1 OUT TO CUSTOMER Completed
10/07/2005 SUE REEVES REJECT SHELF Completed