Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2005 DOUG WILLIAMS ENGINEERING REVIEW Denied SUBJECT: Floodplain Use Permit review - 4563 S. Park Ave.
DATE: 22 June 2005
ACTIVITY NUMBERS: T5OT01314/T05CM00552
T14S, R14E, Section 31

Engineering Division has reviewed the Subject item (drainage report). Approval is not recommended at this time. Tucson Code, Section 26-11.2 (i) requires an engineering study review fee of $150.00 (including review of first resubmittal). Please provide this fee and a revised drainage report addressing the comments provided below.

1. Provide notation that the owner/developer agrees to (1) have an Arizona Registered Professional Land Surveyor certify the lowest floor elevations of the new structure within the floodplain; and (2) obtain a floodplain use permit from City Engineering - Development Services Department (DS 10-02, Sec. 5.2.6).
2. Please provide specific erosion protection recommendations for the building pad/fill during the 100-year storm event. Both temporary and permanent measures for sediment and erosion control must be clearly delineated on plans or other written documents prior to receiving a floodplain use permit (Tucson Code, Section 26-11.2 b)

If you have any questions, I can be reached at 791-5550, ext. 1189 or via email at: Doug.williams@tucsonaz.gov.

Doug Williams
Sr. Eng. Associate
Engineering Division
Development Services Department