Permit Number: T05OT01284
Parcel: 127022350

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T05OT01284
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
07/22/2005 CRAIG GROSS ZONING REVIEW Approved Zoning
7/27/2005
1) Revise the number of parking spaces along the south lot line (from 7 to 6),
2) PAAL north of drying canopy must be marked as "one-way",
3) Revise FAR to exclude all canopies.
07/27/2005 PATRICIA GEHLEN ZONING HC SITE REVIEW Approved
07/28/2005 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Any vegetation higher than thirty (30) inches must be located outside of the sight visibility triangle per LUC 3.7.3.4. Pineapple Guava (Feijoa Sellowiana) will typically grow in excess of 4'. Replace plants or revise planting plan as necessary.

2. A 6' wall to screen loading zone from Speedway Blvd is required per LUC 3.7.2-I. Show the wall on the landscape, site, and grading plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/28/2005 SUE REEVES OUT TO CUSTOMER Completed