Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SITE
Permit Number - T05OT01284
Review Name: RESUBMITTAL - SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/22/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 07/22/2005 | CRAIG GROSS | ZONING | REVIEW | Approved | Zoning 7/27/2005 1) Revise the number of parking spaces along the south lot line (from 7 to 6), 2) PAAL north of drying canopy must be marked as "one-way", 3) Revise FAR to exclude all canopies. |
| 07/27/2005 | PATRICIA GEHLEN | ZONING HC SITE | REVIEW | Approved | |
| 07/28/2005 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | 1. Any vegetation higher than thirty (30) inches must be located outside of the sight visibility triangle per LUC 3.7.3.4. Pineapple Guava (Feijoa Sellowiana) will typically grow in excess of 4'. Replace plants or revise planting plan as necessary. 2. A 6' wall to screen loading zone from Speedway Blvd is required per LUC 3.7.2-I. Show the wall on the landscape, site, and grading plans. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/28/2005 | SUE REEVES | OUT TO CUSTOMER | Completed |