Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05OT01149
Parcel: 108200060

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05OT01149
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2005 LOREN MAKUS ENGINEERING REVIEW Denied DATE: June 15, 2005
TO: Derek Roberts, Arcadis
SUBJECT: Limberlost Townhouses, Grading Plan Review
REVIEWER: Loren Makus
ACTIVITY NUMBER: T05BU00673 and T05OT01149

SUMMARY: The Grading Plan and Stormwater Pollution Prevention Plan were reviewed by Development Services Department Engineering Division. The Grading Plan and Stormwater Pollution Prevention Plan (SWPPP) were not approved at this time.
Grading Plan comments:
1. The grading plan and Floodplain Use Permit can be approved once the SWPPP comments have been adequately addressed.
Stormwater Pollution Prevention Plan comments:
2. Part IV.C.3.c-d. Identify on the map locations of structural and nonstructural controls identified in the SWPPP. Show areas and methods of interim and permanent stabilization that will be used on the site. Straw bales and silt fence are not stabilization practices.
3. Part IV.C.3.g. Identify on the map locations where stormwater is discharged to an MS4. Clearly label the discharge location.
4. Part IV.H.4. Since the discharge location from the site is not easily accessible, describe how the sediment that is discharged to the storm drain will be routinely removed and describe how the eventual location of the discharge to First Avenue Wash will be inspected and sediment that originates from the project site will be routinely removed.
Revise the Grading Plan and prepare a SWPPP to address all of these comments and resubmit three copies of the grading plan and three copies of the SWPPP. If you would like to meet with me to discuss any of these comments please call me at (520) 791-5550 ext. 1161 or email me at loren.makus@tucsonaz.gov.

Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2005 KMEDINA1 OUT TO CUSTOMER Completed