Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: FLOODPLAIN
Permit Number - T05OT00528
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/08/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | DATE: April 8, 2005 ACTIVITY NUMBER: T05OT00528/T05MH00030 PROJECT NAME: Estrella Heights Lot 3 PROJECT ADDRESS: 155 East Placita Estrella PROJECT REVIEWER: Patricia Gilbert SITE PLAN/FLOODPLAIN USE PERMIT IS DENIED RESUBMITTAL REQUIRED: SITE PLAN, FLOODPLAIN USE PERMIT APPLICATION 1. The water surface elevation, lowest structural member and the finish floor elevation must be on the site/plot plan. Per the tentative plat, S99-059, the water surface elevation is 2339.21. The lowest structural member is 2338.25 and the finish floor elevation is 2339.50. 2. Include the City of Tucson datum used for the above referenced elevations. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/12/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 04/12/2005 | SUE REEVES | REJECT SHELF | Completed |