Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05OT00363
Parcel: 114516920

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05OT00363
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: Rick Thornhill DATE: April 14, 2005
Owner
3352 S. Palo Verde
Tucson, Arizona 85713

SUBJECT: 8753 E. Honey Bear Place
Site plan T05CM00712 (Second Review)
Flood Plain Use Permit T05OT00363 (Second Review)
T13S, R15E, Section 34

RESUBMITTAL REQUIRED: Site Plan and Flood Plain Use Permit.

The Site Plan (SP) and Flood Plain Use Permit (FUP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16. Per previous comment.
3. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17. Per previous comment.
4. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number
per D.S. 2-02.2.1.23. Per previous comment.
5. Minimum Finished Floor Elevation shall be 2534.0. List Datums and calculations for the elevation conversion listed.
6. Add drainage blocks to rear wall. Call out the spacing and size.


Flood Plain Use Permit:
1. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number
per D.S. 2-02.2.1.23.
2. Minimum Finished Floor Elevation shall be 2534.0. List Datums and calculations for the elevation conversion listed. Per previous comment.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/8753 E. Honey Bear Place site 2