Permit Number: T05OT00311
Parcel: Unknown

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T05OT00311
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2005 MATT FLICK ENGINEERING REVIEW Denied T05OT00311 - DSD Engineering Comments

Note: Currently, there is no permittable activity associated with this project. The purpose of this submittal and review is to establish possible development scenarios for future development.

1. If results of the BSMF submittals are used, the consultant should state that they accept these results.

2. The proposed channel along the east side of the property appears to be, primarily, on another parcel. Permission must be obtained from the adjacent property owner for construction on that property.

3. Address maintenance of the offsite drainage channel. The hydraulic analyses assume an n-value typical of clean earthen channels. Inspection of the area shows that the channels, in general, are poorly maintained and would not have a n-value typical of clean earthen channels.

4. Explain the use of ineffective flow areas in the right overbank area of the existing conditions HEC-RAS analysis for RS 9-11.

Matt Flick, PE
Engineering Manager

25MAR05

Final Status

Task End Date Reviewer's Name Type of Review Description
05/05/2005 BETH GRANT OUT TO CUSTOMER Completed
05/05/2005 ANGIE SHOFFSTALL REJECT SHELF Completed