Permit Number: T05OT00224
Parcel: 122070710

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T05OT00224
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: February 7th, 2005
ACTIVITY NUMBER: T05OT00224/TO5CM00424
PROJECT NAME: Guest House
PROJECT ADDRESS: 4433 East Waverly Street
PROJECT REVIEWER: Patricia Gilbert

FLOODPLAIN USE PERMIT AND SITE PLAN IS DENIED

RESUBMITTAL REQUIRED: SITE PLAN, DRAINAGE REPORT, FLOODPLAIN USE PERMIT APPLICATION


1. The finish floor elevation on the site plan must match the recommended FFE in the Drainage Report. The drainage report recommends an FFE of 2465.0 NGVD29. The site plan indicates an FFE of 2464.50 NGVD29. Revise the site plan to show the recommended FFE in the drainage report.

2. Add a general note to the site plan stating the entire property is in FEMA Flood Hazard AE.

3. Please note a condition of this permit contains a requirement that the applicant, or the applicant's authorized representative, complete a FEMA Elevation Certificate and is returned to DSD Engineering prior to approval of special inspection.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/11/2005 TAMI ACHONG OUT TO CUSTOMER Completed
02/11/2005 ANGIE SHOFFSTALL REJECT SHELF Completed