Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL02490
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/19/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05EL02490 12/19/05 1. Provide for grounding for Second Buildings per NEC 250.32. It shall be explicit on the plans whether 250.32 (B) (1) or 250.32 (B) (2) is applicable, and compliance with such shall be explicit. 2. Size the Main Bonding Jumper at 2/0. Reference NEC Table 250.66. 3. The note to the Grounding Electrode Conductor, "# 1/0 GRN &" appears to be incomplete. If so, please clarify. |