Permit Number: T05EL02403
Parcel: 10408076F

Address:
4405 N ORACLE RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T05EL02403
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05EL02403 12/5/05

1. Lighting Fixture Schedule is incomplete. Provide power requirements for all fixtures.
2. Clarify which circuits all track lighting is to go on. A couple of them, on the left side of the Lighting Floor Plan, are depicted floating independently with no connection.
3. Minimum font size is 10 point, or a bit over 1/8".
4. Account for continuous loading and largest motor in panel load calculations. Connected loads and demand loads are shown as the same. And it appears that Phase A is overloaded even before this is taken into consideration.