Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL02403
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05EL02403 12/5/05 1. Lighting Fixture Schedule is incomplete. Provide power requirements for all fixtures. 2. Clarify which circuits all track lighting is to go on. A couple of them, on the left side of the Lighting Floor Plan, are depicted floating independently with no connection. 3. Minimum font size is 10 point, or a bit over 1/8". 4. Account for continuous loading and largest motor in panel load calculations. Connected loads and demand loads are shown as the same. And it appears that Phase A is overloaded even before this is taken into consideration. |