| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/28/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05EL02266 11/23/05 1. New Fire system pump is counted at 4800VA, or 20A. If installed on a 20A Circuit Breaker, the concern is that of nuisance tripping. Provide power requirements for the fire pump, along with manufacturer recommendations for overcurrent protection. 2. Verify availability of 20A disconnect switch. |