Permit Number: T05EL02266
Parcel: 136074040

Address:
2002 S CATHY AV

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T05EL02266
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05EL02266 11/23/05

1. New Fire system pump is counted at 4800VA, or 20A. If installed on a 20A Circuit Breaker, the concern is that of nuisance tripping. Provide power requirements for the fire pump, along with manufacturer recommendations for overcurrent protection.
2. Verify availability of 20A disconnect switch.