Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL02266
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/10/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05EL02266 11/10/05 1. Show location of electric service panel on plans. 2. Provide disconnect for Pressure Pump per NEC 430 Part IX. 3. Provide conduit and conductor size and type. 4. Provide load calculations for the electrical service. |