Permit Number: T05EL02266
Parcel: 136074040

Address:
2002 S CATHY AV

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T05EL02266
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05EL02266 11/10/05

1. Show location of electric service panel on plans.
2. Provide disconnect for Pressure Pump per NEC 430 Part IX.
3. Provide conduit and conductor size and type.
4. Provide load calculations for the electrical service.