Permit Number: T05EL02136
Parcel: 108240850

Address:
2494 E RIVER RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T05EL02136
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05EL02136 10/20/05

THERE IS SOME CONFUSION AS TO WHAT IS INTENDED FOR THIS PERMIT (NEW) AND WHAT MAY BE DESIGNATED FOR FUTURE. FOR EXAMPLE:

1. The 400:5 CT Can on Electrical Plan is to be fed from new service. The Line Diagram and Site Plan only call for the empty 4" conduit for a FUTURE new service lateral.
2. A New CT Can is shown on the Line Diagram. Rated 42K. Show Fault Calculations.
3. New Panel MDP is shown on Line Diagram. Provide a fully developed panel schedule for such new panel.
4. Show fault calculations for Fault #4.
5. Mark the remainder of the equipment with designators "Existing", "New", "Future", or make such indication as "Existing Unless Otherwise Noted" on Electrical Plan and One Line Diagram.