Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL02136
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/26/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05EL02136 10/20/05 THERE IS SOME CONFUSION AS TO WHAT IS INTENDED FOR THIS PERMIT (NEW) AND WHAT MAY BE DESIGNATED FOR FUTURE. FOR EXAMPLE: 1. The 400:5 CT Can on Electrical Plan is to be fed from new service. The Line Diagram and Site Plan only call for the empty 4" conduit for a FUTURE new service lateral. 2. A New CT Can is shown on the Line Diagram. Rated 42K. Show Fault Calculations. 3. New Panel MDP is shown on Line Diagram. Provide a fully developed panel schedule for such new panel. 4. Show fault calculations for Fault #4. 5. Mark the remainder of the equipment with designators "Existing", "New", "Future", or make such indication as "Existing Unless Otherwise Noted" on Electrical Plan and One Line Diagram. |