Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL02041
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/18/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05EL02041 107/05 1. Plans do not provide sufficient information to determine whether another service may be permitted to this building. Reference NEC 230.2. Willing to discuss at 791.5550 x1106, or email at Linda.Buczynski@tucsonaz.gov. In any case, placards need to be speficied per NEC 230.2 (E). 2. Provide locations of existing panels. 3. Remove redundant #8 GNDs between service disconnects and gutter. 4. City does not normally allow the "Up-Over-Down" method for attenuating fault current, but occasionally does so in cases such as this. Please specify RK1 as the fuse used in the disconnects. |