Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05EL02041 107/05

1. Plans do not provide sufficient information to determine whether another service may be permitted to this building. Reference NEC 230.2. Willing to discuss at 791.5550 x1106, or email at Linda.Buczynski@tucsonaz.gov. In any case, placards need to be speficied per NEC 230.2 (E).
2. Provide locations of existing panels.
3. Remove redundant #8 GNDs between service disconnects and gutter.
4. City does not normally allow the "Up-Over-Down" method for attenuating fault current, but occasionally does so in cases such as this. Please specify RK1 as the fuse used in the disconnects.