Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/05/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05EL01882 10/5/05 1. Please se Plans Examiner annotations of plans for correction of series-rating notes, clarification that branch circuit loads are existing, conductor type on building exterior. 2. Since the intent is to feed the existing exterior panels, according to the Owner, show such panels and diagram the new feeders to these panels. 3. Provide amperage and fault current rating of existing Panels referenced in Comment #2 above. |