Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05EL01882
Parcel: 11710033A

Address:
351 N COURT AV

Review Status: Completed

Review Details: OTHER

Permit Number - T05EL01882
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05EL01882 10/5/05

1. Please se Plans Examiner annotations of plans for correction of series-rating notes, clarification that branch circuit loads are existing, conductor type on building exterior.
2. Since the intent is to feed the existing exterior panels, according to the Owner, show such panels and diagram the new feeders to these panels.
3. Provide amperage and fault current rating of existing Panels referenced in Comment #2 above.