Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05EL01882
Parcel: 11710033A

Address:
351 N COURT AV

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T05EL01882
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05EL01882 9/14/05

1. Put job address on all sheets.
2. Produce a scaled drawing of apartment unit(s) for the purpose of documenting the upgrade (bringing to Code compliance) of branch circuit loads.
3. Provide conduit and conductor size and type.
4. Provide load calculations for feeders and service. Suggest that future be taken into consideration. Suggest that NEC 220.30 be used for the separate units. You may use 220.32 for the service.
5. Size equipment grounding conductors per NEC Table 250.122, and grounding electrode conductor per NEC 250.66.
6. Provide TEP available fault current, and fault current rating of all new equipment.
Indicate voltage levels.