Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL01882
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/14/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05EL01882 9/14/05 1. Put job address on all sheets. 2. Produce a scaled drawing of apartment unit(s) for the purpose of documenting the upgrade (bringing to Code compliance) of branch circuit loads. 3. Provide conduit and conductor size and type. 4. Provide load calculations for feeders and service. Suggest that future be taken into consideration. Suggest that NEC 220.30 be used for the separate units. You may use 220.32 for the service. 5. Size equipment grounding conductors per NEC Table 250.122, and grounding electrode conductor per NEC 250.66. 6. Provide TEP available fault current, and fault current rating of all new equipment. Indicate voltage levels. |