Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM01627 8/8/05
1. Provide fault current rating of all new equipment.
2. Provide TEP available fault current at point of service.
3. Demonstrate that all equipment is installed with its fault current rating.
4. Indicate on the plans whether the existing service is OH or UG. In the case where existing service is underground, new service shall be underground.
5. Provide a scaled site plan with all equipment.
6. Specify all new equipment. It shall be clear on the plans which disconnects or panels are new and which are existing.
7. #2 Al ampacity 90A. Not protected.