Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL01627
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/09/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM01627 8/8/05 1. Provide fault current rating of all new equipment. 2. Provide TEP available fault current at point of service. 3. Demonstrate that all equipment is installed with its fault current rating. 4. Indicate on the plans whether the existing service is OH or UG. In the case where existing service is underground, new service shall be underground. 5. Provide a scaled site plan with all equipment. 6. Specify all new equipment. It shall be clear on the plans which disconnects or panels are new and which are existing. 7. #2 Al ampacity 90A. Not protected. |