Permit Number: T05EL01606
Parcel: 11504359A

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T05EL01606
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05EL01606 8/5/05

1. Although 175' was used to arrive at the value of F1, the plans scale out to be 150'; the "c" value used appears to pertain to steel conduit. Both combined may yeild an AFC which exceeds the 22K rating of the existing CT can.
2. Applicant indicates that "New" mechanical equipment is intended for future installation. If such is the case, please designate all such equipment as "Future". Otherwise, Mechanical plans shall be provided on a combination permit at this time.
3. Note that two sets are necessary.