Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL01512
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/25/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Each new meter shall have its own designation, reflected on the plans, in the field, and in the City, TEP and Pima County systems. Applicant shall go to Pima County Addressing and obtain address designations for each new meter. Take such address designations to the Permit Counter to have them noted in the City computer system. Show proper meter designations on plans. 2. Sheet E3 Keynote 4, the #8 conductor shall be #6 per NEC Table 250.122. 3. On Sheet E6, please indicate whether Panel F is MCB or MLO. 4. Show panel locations on plans. 5. Document all branch circuits on all panels, since these are all new panels per Note 2 SCOPE OF WORK on Sheet E1. 6. Load calculations for entire new service appear to be low, at 91A for a 600A service. Please verify that such is the case. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/26/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |