Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. Addressing needs to be provided for all three meters. Our system indicates only one address. Applicant shall go to Pima County addressing, then to Permit clerks in City DSD with addressing. Please indicate specific addressing on plans for each meter.
2. Applicant has indicated that New Panel D is Future, not in present contract. If such is the case, please label it "Future."
3. Please put the following note on the plans: "Contractor shall lock out disconnect for future Panel D."
4. The 1/0 GND in the run between the TEP Transformer and the 1200A landing can is a redundant path to ground. Please remove.
5. The #2 GND in the run between the new gutter and the new 400A meter is a redundant path to ground. Please remove.
6. The #6 GND in the run between the new gutter and the new 200A meter is a redundant path to ground. Please remove.
7. Main bonding jumpers in all disconnects sized per NEC 250.102 (C). (3) (600) = 1800 (0.125) = 225. Next size up is 250 per Table 8.