Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL01180
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/14/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05EL01180 6/13/05 1. On Panel Schedule A the bus indicates MLO. Please delete this, as it is MCB. 2. If the lights are existing, state so on the plans. If not, provide conductor and conduit size and type, and demonstrate compliance with the Tucson Lighting Ordinance, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. 3. Show grounding per NEC 250.32 Second Building or Structure. 4. Please clarify the load calculation for the 3 appt's at 239 SF EA. Does not appear to correlate with plan view. By the panels, it appears that there 7 apartments in the west building, two of which do not have the SF indicated on the plans. 5. Call the the N-G MBJ to be a #2, per NEC Table 250.66. Sizing of the Grounding Electrode Conductor to the ground rods is fine. |