Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL01146
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/13/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05EL01146 DENIED 6/8/05 1. Regarding the receptacles for the sign connection, verify that this equipment is cord-connected. 2. Provide for grounding of the new transformer as a Separately Derived System per NEC 250.30. 3. It does not appear that the transformer meets the taps rule according to NEC 240.20 (C). 4. It is not clear how the conductor on the secondary of the new transformer is to be protected. |