Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05EL01146
Parcel: Unknown

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T05EL01146
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05EL01146 DENIED 6/8/05
1. Regarding the receptacles for the sign connection, verify that this equipment is cord-connected.
2. Provide for grounding of the new transformer as a Separately Derived System per NEC 250.30.
3. It does not appear that the transformer meets the taps rule according to NEC 240.20 (C).
4. It is not clear how the conductor on the secondary of the new transformer is to be protected.