Permit Number: T05EL01145
Parcel: 13707046D

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T05EL01145
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05EL01145 DENIED 6/8/05
1. Keynote 1 refers to Sheet E6. No such sheet this project.
2. Regarding the receptacles for the sign connection, verify that this equipment is cord-connected.
3. Panel LB Phase B load, with 4.49 VA from Panel LA instead of 3.91, would compute to about 97A, which is very close to loading the panel, so please correct.