Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL01145
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/14/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05EL01145 DENIED 6/8/05 1. Keynote 1 refers to Sheet E6. No such sheet this project. 2. Regarding the receptacles for the sign connection, verify that this equipment is cord-connected. 3. Panel LB Phase B load, with 4.49 VA from Panel LA instead of 3.91, would compute to about 97A, which is very close to loading the panel, so please correct. |