Permit Number: T05EL01082
Parcel: 115151660

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T05EL01082
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05EL01082 DENIED 6/3/05

1. Minimum font size 1/8". Please blow up plans.
2. Provide conductor and conduit size and type for branch circuits. Conduit size and type for service.
3. Provide TEP available fault current, or add the following note: "Contractor shall provide TEP available fault current. All equipment shall be rated for AFC."
4. All services shall be underground unless a waiver is approved. Use the attached form.
5. #3 GND between CT can and L1 consists of a redundant path to ground. Please remove.
6. Show grounding electrode system.