Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL00982
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/06/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05EL00982 DENIED 5/16/05 1. Need two sets of plans. 2. Provide TEP Available Fault Current, or add a note requiring the Contractor to do so. 3. Provide fault current rating of Panel A. The note as written regarding the option to provide the All-in-One only applies to that option. |