Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05EL00914 12/5/05

1. Lighting Fixture Schedule is incomplete. Provide power requirements for all fixtures, and establish correspondence between Code on Lighting Schedule and designations on Lighting Floor Plan.
2. Clarify which circuits track lighting is to go on. They are depicted floating independantly with no connection.
3. Minimum font size is 10 point, or a bit over 1/8".
4. Account for continuous loading and largest motor in panel load calculations. Connected loads and demand loads are shown as the same.