Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T05EL00914
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05EL00914 12/5/05 1. Lighting Fixture Schedule is incomplete. Provide power requirements for all fixtures, and establish correspondence between Code on Lighting Schedule and designations on Lighting Floor Plan. 2. Clarify which circuits track lighting is to go on. They are depicted floating independantly with no connection. 3. Minimum font size is 10 point, or a bit over 1/8". 4. Account for continuous loading and largest motor in panel load calculations. Connected loads and demand loads are shown as the same. |