Review Details: ELECTRICAL
Permit Number - T05EL00716
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/07/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. COMMENTS 1-3 BELOW ARE SATISFIED. 1. Provide TEP Available Fault current on plans. 2. Owner's Panel is not permitted to be calculated according to NEC 220.30. This calculation is for a dwelling unit itself. 3. NEC 220.30 may not be used for multiple dwelling units. The prope Code section is NEC 220.32. Note that table 230.32 is used to determine the demand factor allowed after the tally of Connected Loads has been performed according to 220.32 (C). APPLICANT SHALL GO TO PIMA COUNTY ADDRESSING AND OBTAIN DESIGNATIONS FOR ALL APARTMENTS. ALL UNITS SHALL BE ATTACHED TO THIS PERMIT. INCLUDES ONE OWNER'S PANEL AND EIGHT APARTMENTS. AFTER PIMA COUNTY ADDRESSING, APPLICANT SHALL GO TO CUSTOMER SERVICE REPRESENTATIVES TO HAVE UNITS ATTACHED TO PERMIT. |