Permit Number: T05EL00716
Parcel: 126162370

Address:
460 S BRYANT AV

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T05EL00716
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/15/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied 1. Please verify with Mike Kaiser at TEP 918.8244 that AFC for this service does not exceed the 22,000A rating of the new circuit breakers.
2. The grouping of 7 disconnects on one side of the Tap Box exceeds City Amendment 230.40 Exception 1.
3. This is not a City of Tucson Code issue but per Mike Kaiser at TEP, if the intent is to provide an 800A service, the service will have to be underground.

APPLICANT SHALL GO TO PIMA COUNTY ADDRESSING AND OBTAIN DESIGNATIONS FOR ALL APARTMENTS. ALL UNITS SHALL BE ATTACHED TO THIS PERMIT. INCLUDES ONE OWNER'S PANEL AND EIGHT APARTMENTS. AFTER PIMA COUNTY ADDRESSING, APPLICANT SHALL GO TO CUSTOMER SERVICE REPRESENTATIVES TO HAVE UNITS ATTACHED TO PERMIT.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/12/2005 JMORALE1 OUT TO CUSTOMER Completed
08/12/2005 ANGIE SHOFFSTALL REJECT SHELF Completed